ASW – Switch with automatic selection of input
Block SymbolLicensing group: ADVANCED
Function Description
The ASW block copies one of the inputs u1, …, u4 or one of the parameters p1, …, p4 to the output
y. The appropriate input signal is copied to the output as long as the input signal iSW belongs to
the set
and the parameters are copied when iSW belongs to the set
(i.e.
for
,
for
etc.). If the iSW input signal differs from any of these values (i.e.
or
or
), the
output is set to the value of input or parameter which has changed the most recently. The
signal or parameter is considered changed when it differs by more than delta from its value at
the moment of its last change (i.e. the changes are measured integrally, not as a
difference from the last sample). The following priority order is used when changes occur
simultaneously in more than one signal: p4, p3, p2, p1, u4, u3, u2, u1. The identifier of input
signal or parameter which is copied to the output y is always available at the oSW
output.
The ASW block has one special feature. The updated value of y is copied to all the parameters p1, …, p4. This results in all external tools reading the same value y. This is particularly useful in higher-level systems which use the set&follow method (e.g. a slider in Iconics Genesis). This feature is not implemented in Simulink as there are no ways to read the values of inputs by external programs.
ATTENTION! One of the inputs u1, …, u4 can be delayed by one step when the block is contained in a loop. This might result in an illusion, that the priority is broken (the oSW output then shows that the most recently changed signal is the delayed one). In such a situation the LPBRK block(s) must be used in appropriate positions.
Inputs
u1..u4 | Analog input signals to be selected from | Double (F64) |
iSW | Active signal or parameter selector | Long (I32) |
Outputs
y | The selected analog signal or parameter | Double (F64) |
oSW | Identifier of the selected signal or parameter | Long (I32) |
Parameters
delta | Threshold for detecting a change 1e-06 | Double (F64) |
p1..p4 | Parameters to be selected from | Double (F64) |
[Previous] [Back to top] [Up] [Next]
2023 © REX Controls s.r.o., www.rexygen.com