VIN – Validation of the input signal

Block SymbolLicensing group: STANDARD
PIC

Function Description
The VIN block can be used for verification of the input signal quality in the REXYGEN system. Further details about quality flags can be found in chapter 1.4 of this manual.

The block continuously separates the quality flags from the input u and feeds them to the iqf output. Based on these quality flags and the GU parameter (Good if Uncertain), the input signals are processed in the following manner:

  • For GU = off the output QG is set to on if the quality is GOOD. It is set to QG = off in case of BAD or UNCERTAIN quality.
  • For GU = on the output QG is set to onif the quality is GOOD or UNCERTAIN. It is set to QG = off only in case of BAD quality.

The output yg is equal to the u input if QG = on. Otherwise it is set to yg = sv (substitution variable).

Inputs

u

Input signal whose quality is assessed. The type of the signal is determined upon the connected signal.

Any

sv

Substitute value for an error case

Any

Outputs

yg

Validated output signal (yg = u for QG = on or yg = sv for QG = off)

Any

QG

Indicator of input signal acceptability

Bool

iqf

Complete quality flag separated from the u input signal

Long (I32)

Parameter

GU

Acceptability of UNCERTAIN quality

Bool

off ..

Uncertain quality unacceptable

on ...

Uncertain quality acceptable

2023 © REX Controls s.r.o., www.rexygen.com