GETPR, GETPI, GETPB – Blocks for remote parameter acquirement
Block SymbolsLicensing group: STANDARD
Function Description
The GETPR, GETPI and GETPB blocks are used for acquiring the parameters of other blocks
in the model remotely . The only difference among the three blocks is the type of
parameter which they are acquiring. The GETPR block is used for obtaining real
parameters, the GETPI block for integer parameters and the GETPB block for Boolean
parameters.
The blocks operate in two modes, which are switched by the GETF parameter. For the output y (or k, Y) is set to the value of the remote parameter at the start and every time when the remote parameter changes. If the parameter is set to on, then the blocks work in single-shot read mode. In that case the remote parameter is read only when rising edge (offon) occurs at the GET input.
The name of the remote parameter is determined by the string parameter sc (string connection), which has the form <block_path:parameter_name>. It is also possible to access individual items of array-type parameters (e.g. the tout parameter of the ATMT block). This can be achieved using the square brackets and item number, e.g. .ATMT:touts[2]. The items are numbered from zero, thus the string connection stated above refers to the third element of the array.
The path to the block whose parameter should be read can contain hierarchic levels separated by dots followed by the block name. The path can be either relative or absolute:
- Relative – starts at the level where the GETPR block (or GETPI, GETPB) is located. The string has to be prefixed with ’.’ in this case. Examples of relative paths: ".GAIN:k", ".Motor1.Position:ycn".
- Absolute – complete sequence of hierarchic levels down to the block. For referring to blocks located in the driver task (see the IOTASK block for details on configuration) the ’&’ followed by the driver’s name is used at the beginning of the absolute path. Examples of absolute paths: "task1.inputs.lin1:u2", "&EfaDrv.measurements.DER1:n".
The order and names of individual hierarchic levels are displayed in a tree structure in the REXYGEN Diagnostics program.
Input
GET | Input for initiating one-shot parameter read (offon) | Bool |
Outputs
y | Parameter value, output of the GETPR block | Double (F64) |
k | Parameter value, output of the GETPI block | Long (I32) |
Y | Parameter value, output of the GETPB block | Bool |
E | Error flag | Bool |
|
|
|
Parameters
sc | String connection to the remote parameter respecting the above mentioned notation | String |
GETF | Continuous or one-shot mode | Bool |
|
|
|
[Previous] [Back to top] [Up] [Next]