SWR – Selector with ramp
Block SymbolLicensing group: STANDARD
Function Description
The SWR block selects one of two input signals u1 and u2 with respect
to the binary input SW. The selected input is copied to the output y. If
(),
then the selected signal is u1 (u2). The output signal is not set immediately to the value of the
selected input signal but tracks the selected input with given rate constraint (i.e. it follows a
ramp). This rate constraint is configured independently for each input u1, u2 and is defined by
time constants t1 and t2. As soon as the output reaches the level of the selected
input signal, the rate limiter is disabled and remains inactive until the next signal
switching.
Inputs
u1 | First analog input of the block | Double (F64) |
u2 | Second analog input of the block | Double (F64) |
SW | Signal selector | Bool |
|
|
|
Parameters
t1 | Rate limiter time constant for switching from u2 to u1 1.0 | Double (F64) |
t2 | Rate limiter time constant for switching from u1 to u2 1.0 | Double (F64) |
y0 | Initial output value to start the tracking from (before the first switching of signals occurs) | Double (F64) |
Output
y | Analog output of the block | Double (F64) |