LPF – Low-pass filter
Block SymbolLicensing group: STANDARD
Function Description
The LPF block implements a second order filter in the form
where
and fb and are the block parameters. The fb [Hz] parameter defines the filter bandwidth and xi is the relative damping coefficient. Attenuation at frequency fb is 3 dB, at approximately 40 dB. For the correct function of the filter, must hold, where is the block triggering period. The recommended value is for the Butterworth filter and for the Bessel filter.
If , then the state of the filter is set to the steady value at the block initialization according to the input signal u.
This block propagates the signal quality. More information can be found in the 1.4 section.
Input
u | Input signal to be filtered | Double (F64) |
R1 | Block reset | Bool |
HLD | Hold | Bool |
Parameter
fb | Filter bandwidth [Hz] 1.0 | Double (F64) |
xi | Relative damping coefficient 0.707 | Double (F64) |
ISSF | Steady state at start-up | Bool |
|
|
|
Output
y | Filtered output signal | Double (F64) |
[Previous] [Back to top] [Up] [Next]