LPF – Low-pass filter

Block SymbolLicensing group: STANDARD
PIC

Function Description
The LPF block implements a second order filter in the form

Fs = 1 a2s2 + 2ξas + 1,

where

a = 2 2ξ4 2ξ2 + 1 2ξ2 + 1 2πfb

and fb and ξ = xi are the block parameters. The fb [Hz] parameter defines the filter bandwidth and xi is the relative damping coefficient. Attenuation at frequency fb is 3 dB, at 10 fb approximately 40 dB. For the correct function of the filter, fb < 1 10TS must hold, where TS is the block triggering period. The recommended value is xi = 0.71 for the Butterworth filter and xi = 0.87 for the Bessel filter.

If ISSF = on, then the state of the filter is set to the steady value at the block initialization according to the input signal u.

This block propagates the signal quality. More information can be found in the 1.4 section.

Input

u

Input signal to be filtered

Double (F64)

R1

Block reset

Bool

HLD

Hold

Bool

Parameter

fb

Filter bandwidth [Hz]  1.0

Double (F64)

xi

Relative damping coefficient  0.707

Double (F64)

ISSF

Steady state at start-up

Bool

off ..

Zero initial state

on ...

Initial steady state

Output

y

Filtered output signal

Double (F64)