SEL – Selector switch for analog signals
Block SymbolLicensing group: STANDARD
Function Description
The SEL block is obsolete, replace it by the SELQUAD, SELOCT
or SELHEXD block. Note the difference in binary selector signals
SW.
The SEL block selects one of the four input signals u1, u2, u3 and u4 and copies it to the output signal y. The selection is based on the iSW input or the binary inputs SW1 and SW2. These two modes are distinguished by the BINF binary flag. The signal is selected according to the following table:
iSW | SW1 | SW2 | y |
0 | off | off | u1 |
1 | off | on | u2 |
2 | on | off | u3 |
3 | on | on | u4 |
This block does not propagates the signal quality. More information can be found in the 1.4 section.
Input
u1 | First analog input of the block | Double (F64) |
u2 | Second analog input of the block | Double (F64) |
u3 | Third analog input of the block | Double (F64) |
u4 | Fourth analog input of the block | Double (F64) |
iSW | Active signal selector | Long (I32) |
SW1 | Binary signal selector | Bool |
SW2 | Binary signal selector | Bool |
Parameter
BINF | Enable the binary selectors | Bool |
|
|
|
Output
y | The selected input signal | Double (F64) |
[Previous] [Back to top] [Up] [Next]