CMP – Comparator with hysteresis
Block SymbolLicensing group: STANDARD
Function Description
The CMP block compares the inputs u1 and u2 with the hysteresis h as follows:
where
ek=u1k−u2kand
hyst(ek)={0forek≤−hYk−1forek∈(−h,h)1forek≥h(ek>h for h=0)
The indexed variables refer to the values of the corresponding signal in the cycle defined by the index, i.e. Yk−1 denotes the value of output in the previous cycle/step. The value Y−1 is used only once when the block is initialized (k=0) and the difference of the input signals ek is within the hysteresis limits.
This block propagates the signal quality. More information can be found in the 1.4 section.
Input
u1 | First analog input of the block | Double (F64) |
u2 | Second analog input of the block | Double (F64) |
Parameter
hys | Hysteresis ↓0.0 ⊙0.5 | Double (F64) |
Output
Y | Logical output of the block | Bool |
[Previous] [Back to top] [Up] [Next]